Technical Specifications
- SUN-3K-G06P3-EU-AM2
-
SUN-4K-G06P3-EU-AM2
-
SUN-5K-G06P3-EU-AM2
-
SUN-6K-G06P3-EU-AM2
-
SUN-7K-G06P3-EU-AM2
-
SUN-8K-G06P3-EU-AM2
-
SUN-10K-G06P3-EU-AM2
-
SUN-12K-G06P3-EU-AM2
- Feedback
Model | SUN-3K-G06P3-EU-AM2 | SUN-4K-G06P3-EU-AM2 | SUN-5K-G06P3-EU-AM2 | SUN-6K-G06P3-EU-AM2 | SUN-7K-G06P3-EU-AM2 | SUN-8K-G06P3-EU-AM2 | SUN-9K-G06P3-EU-AM2 | SUN-10K-G06P3-EU-AM2 | SUN-12K-G06P3-EU-AM2 | SUN-15K-G06P3-EU-AM2 |
PV String Input Data | ||||||||||
Max. PV Input Power (kW) | 4.5 | 6 | 7.5 | 9 | 10.5 | 12 | 13.5 | 15 | 18 | 22.5 |
Max. PV Input Voltage (V) | 1100 | |||||||||
Start-up Voltage (V) | 140 | |||||||||
MPPT Voltage Range (V) | 120-1000 | |||||||||
Rated PV Input Voltage (V) | 600 | |||||||||
Max. Operating PV Input Current (A) | 13+13 | 13+26 | ||||||||
Max. Input Short Circuit Current (A) | 19.5+19.5 | 19.5+39 | ||||||||
No. of MPP Trackers/ No. of StringsperMPP Tracker |
2/1+1 | 2/1+2 | ||||||||
AC Output Side | ||||||||||
Rated AC Output Active Power (kW) | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 12 | 15 |
Max.AC Output Apparent Power (kVA) | 3.3 | 4.4 | 5.5 | 6.6 | 7.7 | 8.8 | 9.9 | 11 | 13.2 | 16.5 |
Rated AC Output Current (A) | 4.6/4.4 | 6.1/5.8 | 7.6/7.3 | 9.1/8.7 | 10.7/10.2 | 12.2/11.6 | 13.7/13.1 | 15.2/14.5 | 18.2/17.4 | 22.8/21.8 |
Max. AC Output Current (A) | 5/4.8 | 6.7/6.4 | 8.4/8 | 10/9.6 | 11.7/11.2 | 13.4/12.8 | 15/14.4 | 16.7/16 | 20/19.2 | 25/24 |
Rated Output Voltage/Range (V) | 220/380V, 230/400V 0.85Un-1.1Un | |||||||||
Grid Connection Form | 3L/N/PE | |||||||||
Rated Output Grid Frequency/Range(Hz) | 50/45-55, 60/55-65 | |||||||||
Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | |||||||||
Total Current Harmonic Distortion THDi | <3% | |||||||||
DC Injection Current | <0.5%ln | |||||||||
Efficiency | ||||||||||
Max. Efficiency | 98.1% | 98.2% | 98.3% | 98.5% | ||||||
Euro Efficiency | 97.5% | 97.6% | 97.8% | 98% | ||||||
MPPTEfficiency | >99% | |||||||||
Equipment Protection | ||||||||||
DC Polarity Reverse Connection Protection | Yes | |||||||||
AC Output Overcurrent Protection | Yes | |||||||||
AC Output Overvoltage Protection | Yes | |||||||||
AC Output Short Circuit Protection | Yes | |||||||||
Thermal Protection | Yes | |||||||||
DC Terminal Insulation Impedance Monitoring | Yes | |||||||||
DC Component Monitoring | Yes | |||||||||
Ground Fault Current Monitoring | Yes | |||||||||
Arc Fault Circuit Interrupter (AFCI)
|
Optional
|
|||||||||
Power Network Monitoring | Yes | |||||||||
Island Protection Monitoring | Yes | |||||||||
Earth Fault Detection | Yes | |||||||||
Overvoltage Load Drop Protection | Yes | |||||||||
Residual Current (RCD) Detection | Yes | |||||||||
Surge Protection Level | TYPE II(DC),TYPE II(AC) | |||||||||
Interface | ||||||||||
Communication Interface | RS485/RS232 | |||||||||
Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | |||||||||
General Data | ||||||||||
Operating Temperature Range (°C) | -25 to +60℃, >45℃ Derating | |||||||||
Permissible Ambient Humidity | 0-100% | |||||||||
Permissible Altitude (m) | 4000m | |||||||||
Noise (dB) | <45 | |||||||||
Ingress Protection(IP) Rating | IP 65 | |||||||||
Inverter Topology | Non-Isolated | |||||||||
Over Voltage Category | OVC II(DC), OVC III(AC) | |||||||||
Cabinet Size (WxHxD mm) | 283×463×178 (Excluding Connectors and Brackets) | |||||||||
Weight (kg) | 11 | |||||||||
Warranty | 5 Years | |||||||||
Type of Cooling | Natural Cooling | |||||||||
Grid Regulation | IEC 61727, IEC 62116,CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98,G99,VDE-AR-N 4105 |
|||||||||
Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |